Rheem R-410A Dokumentacja

Przeglądaj online lub pobierz Dokumentacja dla Klimatyzatory typu split Rheem R-410A. Rheem R-410A Specifications Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 28
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
92-21354-78-07
SUPERSEDES 92-21354-78-06
13 & 14.5 SEER SERIES
CONDENSING UNITS
1
1
2 - 5 TONS FEATURING INDUSTRY
STANDARD R-410A REFRIGERANT R-410
INSTALLATION INSTRUCTIONS
NOTE: Appearance of unit may vary.
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!
!
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
WARNING
!
THESE INSTRUCTIONS ARE INTENDED AS AN AIDTO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR
PROPER INSTALLATION, ADJUSTMENT AND OPERA-
TION OF THIS UNIT. READ THESE INSTRUCTIONS
THOROUGHLY BEFORE ATTEMPTING INSTALLATION
OR OPERATION. FAILURE TO FOLLOW THESE
INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLA-
TION, ADJUSTMENT, SERVICE OR MAINTENANCE
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ISO 9001:2008
Przeglądanie stron 0
1 2 3 4 5 6 ... 27 28

Podsumowanie treści

Strona 1 - INSTALLATION INSTRUCTIONS

92-21354-78-07SUPERSEDES 92-21354-78-0613 & 14.5 SEER SERIESCONDENSING UNITS11⁄2 - 5 TONS FEATURING INDUSTRYSTANDARD R-410A REFRIGERANT R-410INSTA

Strona 2 - TABLE OF CONTENTS

106.0 REPLACEMENT UNITSTo prevent failure of a new condensing unit, the existing evaporator tubing systemmust be correctly sized and cleaned or replac

Strona 3 - 1.0 SAFETY INFORMATION

11the unit and 15 feet of standard size interconnecting liquid and vapor lines. For dif-ferent lengths, adjust the charge as indicated below.1/4” ± 0.

Strona 4 - 2.0 GENERAL

• If tubing is to be run underground, it must be run in a sealed watertight chase.• Use care in routing tubing and do not kink or twist. Use a tubing

Strona 5 - AIR INLETS

131/4 [6.4] 25 [7.6] 40 [12.2] 25 [7.6] 9 [2.7] N/A N/A11⁄2 Ton 3/8” [9.5] 5/16 [7.9] 25 [7.6] 50 [15.2] 62 [18.9] 58 [17.7] 53 [16.2] 49 [14.9]3/8* [

Strona 6

1410.0 EVACUATION PROCEDUREEvacuation is the most important part of the entire service procedure. The life andefficiency of the equipment is dependent

Strona 7 - 3.0 LOCATING UNIT

1513.0 CHECKING REFRIGERANT CHARGECharge for all systems should be checked against the Charging Chart inside theaccess panel cover. Before using the c

Strona 8

13.3 FINAL LEAK TESTINGAfter the unit has been properly evacuated and charged, a halogen leak detectorshould be used to detect leaks in the system. Al

Strona 9 - 5.0 SERVICING R-410A MODELS

15.0 FIELD INSTALLED ACCESSORIES15.1 COMPRESSOR CRANKCASE HEAT (CCH)While scroll compressors usually do not require crankcase heaters, there areinstan

Strona 10 - 9.0 INTERCONNECTING TUBING

1815.4 HIGH AND LOW PRESSURE CONTROLS (HPC & LPC)These controls keep the compressor from operating in pressure ranges which cancause damage to the

Strona 11 - 9.5 TUBING INSTALLATION

1917.0 TROUBLE SHOOTINGIn diagnosing common faults in the air conditioning system, it is useful to presentthe logical pattern of thought that is used

Strona 12 - 9.7 LEAK TESTING

2TABLE OF CONTENTS1.0 SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32.0 GENERAL . . . .

Strona 13

2017.2 MECHANICAL CHECKS FLOW CHARTUnit Running?YESLow Head PressureLow Suction PressureOpen IPR Valve Dirty EvaporatorInadequate AirflowRestricted Fi

Strona 14 - 12.0 CHECKING AIRFLOW

21TABLE 8AIR CONDITIONING SYSTEM TROUBLESHOOTING TIPSAIR CONDITIONING SYSTEMTROUBLESHOOTING TIPS17.3 SUPERHEAT CALCULATION1. Measure the suction press

Strona 15 - 13.2 CHARGING BY WEIGHT

22SYMPTOM POSSIBLE CAUSE REMEDYUnit will not run • Power off or loose electrical connection • Check for correct voltage at contactor in condensing uni

Strona 16 - 14.0 ELECTRICAL WIRING

23FIGURE 318.1 PSC OD FAN MOTORSINGLE-PHASE WIRING DIAGRAM01-19-04JHB90-101229-010118.0 WIRING DIAGRAMS

Strona 17 - 15.2 TIME DELAY CONTROL (TDC)

24FIGURE 418.2 ECM OD FAN MOTOR

Strona 18 - 16.0 SERVICE

25FIGURE 518.3 PSC OD FAN MOTORTHREE-PHASE WIRING DIAGRAMWIRING DIAGRAM6C (T1)S (T2)R (T3)(BK)(PR)(S)C (T1)S (T2)R (T3)OPT.AUXG / YGND.CCHOPT.WIRING S

Strona 22 - TROUBLE SHOOTING CHART

31.0 SAFETY INFORMATION!WARNINGTHE MANUFACTURER’S WARRANTY DOES NOT COVER ANY DAMAGE ORDEFECT TO THE HEAT PUMP CAUSED BY THE ATTACHMENT OR USE OFANY C

Strona 23 - 90-101229-01

42.0 GENERALThe information contained in this manual has been prepared to assist in the properinstallation, operation and maintenance of the air condi

Strona 24 - FIGURE 4

5FIGURE 1DIMENSIONSDIMENSIONAL DATAAIR DISCHARGE: ALLOW60” MINIMUM CLEARANCE.LHSEE DETAIL AwA-00008SERVICE ACCESSALLOW 24” CLEARANCEAIR INLETS(LOUVERE

Strona 25 - FIGURE 5

6TABLE 1ELECTRICAL AND PHYSICAL DATA – 13 SEER2.4 ELECTRICAL & PHYSICAL DATA (SEE TABLE 1)Electrical PhysicalModelNumber13 SEER3-PHASE208/230VPhas

Strona 26

73.0 LOCATING UNIT3.1 CORROSIVE ENVIRONMENTThe metal parts of this unit may be subject to rust or deterioration if exposed to acorrosive environment.

Strona 27

8NOTE: These units must be installed outdoors. No ductwork can be attached, orother modifications made, to the discharge grille. Modifications will af

Strona 28

94.0 REFRIGERANT CONNECTIONSAll units are factory charged with Refrigerant 410A. All models are supplied withservice valves. Keep tube ends sealed unt

Komentarze do niniejszej Instrukcji

Brak uwag